Dwyer Series MSX MAGNESENSE® Differential Pressure Transmitter
Dwyer Series MSX MAGNESENSE® Differential Pressure Transmitter
The Series MSX Magnesense® Differential Pressure Transmitter combines the stability and versatility of the original Series MS2 Magnesense® II transmitter for use in building control applications. Pressure ranges are available in Pa, mm w.c., and in w.c. All pressure ranges can be configured in unidirectional or bidirectional modes, providing a total of 32 ranges. The MSX transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability for calculating flow. Dual voltage and milliamp output signals can be used to provide both control and equipment output signal verification.
- Read LCD values easier with rotatable 180° display
- Quick and easy wiring via the optional toolless terminal block
- Add safety to variety of applications with UL94 V-0 and plenum ratings
|
Service |
Air and non-combustible, compatible gases. |
|
Wetted Materials |
Consult factory. |
|
Accuracy |
±1% FSO. |
|
Stability |
±1% FSO/year. |
|
Temperature Limits |
-4 to 158°F (-20 to 70°C). |
|
Pressure Limits |
Ranges 0 and 1: 3.6 psi (24.8 kPa) max operation, 6 psi (41.3 kPa) burst; Ranges 2, 3 and 4: 6 psi (41.3 kPa) max operation, 6 psi (41.3 kPa) burst. |
|
Power Requirements |
10-36 VDC (2-wire), 17-36 VDC or isolated 21.6-33 VAC (3-wire). |
|
Output Signals |
4-20 mA (2-wire); 0-10 V or 0-5 V selectable (3-wire). |
|
Response Time |
Instantaneous (default) or 3 s (selectable). |
|
Electrical Entry |
1/2" NPS thread. |
|
Display (optional) |
4 digit LCD. |
|
Process Connections |
1/8", 3/16", 1/4", 5 mm, and 6 mm ID flexible tubing. |
|
Weight |
8.0 oz (230 g). |
|
Agency Approvals |
CE. |